Price
$1,205.00
CAD
/ each
Stock
100+ In Stock
Does not ship to OH, United States
- Agency Approvals - ATEX II (1)G [Ex Ia] IIC, II (1)D [Ex Ia D] + Ship Approval
- Communication - Without
Specifications
Brand
Accuracy
- 0.1 % of 20 mA (± 20 µA)
Ambient Temperature Range
- -20° to 60° C (-4° to 140° F)
Applications
- Gauge
- Level
- Process Pressure
- Remotete Enquiry of Measured Values
- Value Indication & Adjustment of 4-20 mA / HART Sensors
Approvals & Certifications
- ATEX
- CSA
- FM
- GOST
- IEC
Communication
- 10/100 MegaBits - Data Transmission
Configuration
- HART Protocol - Digital for VEGA HART Sensors
Consumption
- 12 VA - Max.
- 7.5 W - Max.
Display
- LCD Display - 50 x 25 mm, Digital & QuasiAnalog Display
Electrical Connectors
- 16 AWG, (1.5 mm²) - Max.
- Screw Terminal
Environmental Protection
- IP20
- IP30
Hysteresis
- Adjustable
Indication
- Green LED - Status Interface
- Green LED - Status, Operating Voltage
- Red LED - Status, Fault Signal
- Yellow LED - Status Operating Relay 1/2/3
Input
- 4-20 mA (HART) x 1 - Number of Sensors Input
- Active Sensor - Sensor Supply through Vegamet 624
- Passive Sensor - Sensor Has an Own Power Supply
Interface Connection
- Ethernet Interface - 1 X, cannot be combined with RS-232
- RS-232 Interface - 1 X, cannot be combined with Ethernet
Loop Resistance
- 500 ohms - Max.
Mounting
- Carrier Rail (35 x 7.5 According to DIN EN 50022 / 60715)
Operating Voltages
- 20-253 Vac
- 20-253 Vdc
- 50/60 Hz
Output
- 0-20 mA - Current Outputs
- 4-20 mA - Current Outputs
Relay Output
- Breaking Capacity: 50 mW Min., 750 VA AC, 54 W DC, Max.
- Quantity: 3 x Operating Relay, 1 x Fail-safe Relay
- Switching Current: 10 µA DC Min., 3 A AC, 1 A DC, Max.
- Switching Voltage: 10 mVdc Min., 250 Vac/dc, Max.
Sensor Input
- Active Input: Sensor Supply through Vegamet 624
- Number of Sensors 1 x 4-20 mA (HART)
- Passive Input: Sensor Has an Own Power Supply